You can obtain the panel serial number from the label on the panel card or from the system information section in the menu.
You will need the activation code for access level 3 for operations to be performed in the addressable fire detection and control panel menu.
Please take the following instructions into consideration during commissioning. Please take the following instructions into consideration during commissioning.
- The fire panel must be installed on a solid and accessible surface.
- The panel's AC and battery connections must be made properly.
- The grounding line connection of the panel must be made.
- There should be no ground leakage in the loop cables connected to the panel, if there is, the problem should be fixed.
- Loop cables must be connected to the panel properly (both incoming and outgoing).
- Any errors (if any) seen on the screen when the panel is operated must be corrected.
- The cables in the panel loop line should be checked for any short circuits or open circuits.
- Addressing of detectors, modules, buttons and sirens to be connected to the panel should be done before connecting to the loop line.
- All addressed devices should be plugged into their places and made ready for scanning from the panel.
- All devices connected to the system should be detected by scanning the devices from the panel menu.